![]()
ANSI/TIA/EIA-570 Residential Cabling Standard
GRADES OF RESIDENTIAL CABLING
When choosing a cabling system for residential use, a grading system is used.
Each grade supports various applications and services. The grading system
does not apply to home automation and security systems so the designer/installer
should consult the manufacturer's recommendations.
Table 1: Residential Grading System
Grade 1 Grade 2
Services Supported Telephone, Satellite, CATV, data Telephone, Satellite,
CATV, Data, Multimedia and other advanced services.
Cable Types Twisted pair, coaxial Twisted pair, coaxial cable, optional fiber
optic cable
Topology Star Star
Minimum Outlet Configuration 1 4-pair UTP Category 3 or higher and 1 75 ohm
coaxial cable 2-4 pair UTP Category 5 or higher (5e recommended) and 2 75
ohm coaxial cable.
SINGLE RESIDENTIAL UNIT CABLING SYSTEM
Demarcation Point
The demarcation point is the interface point between the telephone company
and/or other network providers and the customer facilities. The demarc point
may be located inside or outside of the house depending on the local regulations.
More and more demarc points are becoming a NID, or Network Interface Device.
This is a small box where the access provider can disconnect the customer
services and test the access providers circuit in the event of a trouble report
(See ADO below). Once the AP proves their circuits are functioning properly,
the home owner then has to check the internal wiring for any problems. The
AP must be notified if the total length of cabling from the demarcation point
to the furthest outlet exceeds 150 m (492 ft).
Auxiliary Disconnect Outlet (ADO)
An auxiliary disconnect outlet (ADO) provides the means for the tenant to
disconnect from an access provider for troubleshooting purposes. The ADO shall
be installed if there is not already a disconnection method, or the existing
location is not easily accessible by the owner/tenant. Where possible the
ADO and distribution device (DD) should be located indoors.
Auxiliary Disconnect Outlet Cable
These are the cables that connect the ADO to the demarcation point. In multi
unit facilities the cable may extend from the floor serving terminal to the
ADO in the tenants unit.
Distribution Device (DD)
The DD is the central point to which all horizontal cables are terminated
and cross connected to the various services used by the owner. The DD houses
all of the cables and hardware required to affect proper termination and cross
connection. Space for surge suppression should be located next to, or within
the DD for each conductive cable entering or leaving the building. Access
to the building electrical ground shall be provided within 1.5 m (5 ft) of
the DD, and in accordance with applicable local and/or national codes. The
DD may consist of a passive cross-connect facility, or an active cross-connect
facility, or both.
Location Requirements
The DD:
shall be installed in a accessible location inside the tenant's space
should be centralized to minimize the length of outlet cables
may be mounted on a backboard, or recessed between stud spaces
Table 2: Space Allocation
Number of Outlets/Connectors Grade 1 Grade 2
1-8 410 mm (16") wide
610 mm (24") high 815 mm (32") wide
915 mm (36") high
9-16 410 mm (16") wide
915 mm (36") high 815 mm (32") wide
915 mm (36") high
17-24 410 mm (16") wide
1220 mm (48") high 815 mm (32") wide
1220 mm (48") high
24 plus 410 mm (16") wide
1525 mm (60") high 815 mm (32") wide
1525 mm 1525 mm (60") high
Note:There are manufacturers of home structured media products who offer a
box to locate the various media and services. These boxes can be located between
studs (normally 16" centers) and therefore the above table would not
pertain to their products. However check with the manufacturer for specifications
on terminating planned and future services.
Electrical Power
An electrical outlet:
should be installed regardless of the grade of service
should be a dedicated 15 Amp, 120 Volt, non-switchable duplex electrical outlet
located within 1.5 m (5 ft) of the DD
should be at a convenient height
shall be in compliance with applicable codes
Outlet Cable
Outlet cables are the same as horizontal cables found in commercial buildings.
They connect the DD to the telecommunications outlets. As in commercial cabling
a transition point or consolidation point may be used. (See also Training-Work
Area Outlets) As in commercial applications, the length of the cable itself
shall not exceed 90 m (295 ft), and the total length of the Outlet Cable and
patch cords shall not exceed 100 m (328 ft)
Recognized Cables
Recognized outlet cable includes:
4-Pair UTP (ANSI/TIA/EIA-568-B.2)
50/125 mm multi-mode fiber
62.5/125 mm multi-mode fiber
Singlemode fiber
Series 6 coaxial (SCTE IPS-SP-001)
Cabling Topology for Outlet Connectors
Outlet cabling shall be placed in a star topology.
Cabling for Fixed Devices
Certain fixed devices, such as intercom, security system keypads, sensors
and smoke detectors may be hard-wired to the fixed device controller. Fixed
devices may be cabled using a star, loop, or daisy-chain topology according
to the manufacturer's recommendations.
Outlet Locations
A minimum of one outlet location shall be cabled in each of the following
rooms (where applicable):
kitchen
each bedroom
family/great room
den/study
it is recommended that an outlet be located in every room, if possible
Outlets:
should be planned to prevent the need for extension cords
should be provided within unbroken wall spaces of 3.7 m (12 ft) or more
should be provided so that no point along the floor line in any wall space
is more than 7.6 m (25 ft), in other words, where a wall is broken by a doorway,
entranceway or other opening (at the floor level), the distance between that
opening and an outlet must be less than 7.6 m (25 ft), when measured horizontally,
from an outlet location in that space shall be mounted at heights in accordance
with applicable codes
Outlet Cable Pathways
In new construction, pathways that conceal the cable shall be used as a means
for placing outlet cable between a DD and the telecommunications outlet box
or mounting bracket. Where possible pathways that conceal the cable are also
recommended for remodeling construction. This can be accomplished by placing
the cables in wall studs and ceiling joists before the walls and ceilings
are sheathed. If the cabling system is large enough, other pathways may be
required such as a tray system. See ANSI/TIA/EIA-569-A for other types of
pathways.
Telecommunications Outlet Connector
The telecommunications outlet connector shall:
be compatible with the media provided at that location
have application specific components such as splitters, amplifiers and impedance
matching devices placed external to the telecommunications outlet connector.
Equipment Cords, Patch Cords and Jumpers
Equipment cords extend from the telecommunications outlet connector to the
terminal equipment connector, or from the DD to electronic equipment. Patch
cords or jumpers are used for interconnections or cross-connections at the
DD. For each channel (see Copper Testing-Channel), a total of 10 m (33 ft)
is allowed for equipment cords and patch cords or jumpers.
MULTI-TENANT/CAMPUS INFRASTRUCTURE
In multi-tenant dwellings:
the demarcation point may be located at either the entrance point of the building
or in the individual tenant space access to shared-use space shall be controlled
by the building owner or agent the access provider shall be notified at the
design stage to accommodate transmission requirements when the total length
of cabling from the demarcation point to the furthest outlet exceeds 150 m
(492 ft)
grounding and bonding shall be performed in accordance with applicable electrical
codes (see ANSI/TIA/EIA-607)
Entrance Facility
The entrance facility:
is made up of the telecommunications service entrance to the building, including
the entrance point through the building wall and continuing to the main terminal
space or equipment room may contain the backbone pathways that link to other
buildings in campus situations (multiple buildings on the same property, eg:
home and detached garage may also include antenna entrances may require primary
protection depending on local requirements should provide for surge protection
for all conductive cables leaving or entering the building shall provide access
to the building's electrical ground with 1.5 m (5 ft) of the conductive cables
All access providers shall be contacted to establish their requirements. For
further information about entrance facilities, see ANSI/TIA/EIA-569-A.
Main Terminal Space
The main terminal space may:
be co-located with the entrance facility also be used to house active equipment
house the demarcation point, ADO cable, and backbone cable house the associated
pathways, protection devices, and any other equipment needed to provide a
connection from the access providers' access lines
Equipment Room
An equipment room:
may house the entrance facility, the main terminal space, and a floor serving
terminal typically houses more equipment than a floor serving terminal and
it has different space requirements requires other support facilities such
as power, heating, ventilation, and air conditioning (HVAC)
For more information on equipment rooms, see ANSI/TIA/EIA-569-A.
Floor Serving Terminal
The floor serving terminal is the space where backbone and ADO cables terminate.
A floor serving terminal:
should be located on each floor, or every third floor
should be in a common area and easily accessible
shall be sized in accordance with table 2
should be able to be expanded in size to accommodate additional hardware.
Table 3: Floor Serving Terminal Space Requirements
Grade 1 Grade 2
Minimum space for first 5 tenants 370 mm (14.5 in) wide
610 mm (24 in) high 775 mm (30.5 in) wide
610 mm(24 in) high
Minimum space for each additional unit 32270 sq. mm
(50 sq. in) 64540 sq, mm
(I00 sq. in)
Backbone Pathways
Planning of the pathways should provide for additional capacity to accommodate
future media requirements, thereby reducing possible construction interference.
lntrabuilding Backbone Pathways
lntrabuilding pathways use conduits, sleeves, slots, or cable trays as a means
for placing backbone cable. Where backbone cable extends from the main terminal
space to a floorserving terminal space, a minimum of one 100 (4) trade size
conduit or sleeve shall be provided for each backbone pathway. Where cable
bundles with an equivalent diameter of 25 mm (1 in) or less extend through
each apartment closet, a minimum of one 40 (1-1/2) trade size conduit or sleeve
shall be provided for the backbone pathways. For more information on intrabuilding
backbone pathways, see ANSI/TIA/EIA-569-A.
Interbuilding Telecommunications Backbone Pathways
lnterbuilding telecommunications backbone pathways provide a means of interconnecting
separate buildings. Routing for these pathways may be:
underground
buried
aerial
tunnels
For more information on interbuilding telecommunications backbone pathways,
see ANSI/TIA/EIA-758.
Backbone Cabling
Recognized Cables
Recognized backbone cables include:
100-ohm twisted-pair (ANSI/TIA/EIA-758 and ANSI/TIA/EIA-568-B)
50/125 µm multi-mode fiber
62.5/125 µm multi-mode fiber
Singlemode fiber
Hard-line coaxial (SCTE IPS-SP-100)
Series 6 and 11 coaxial (SCTE IPS-SP-001)
Topology
When using twisted pair and optical fiber, a star topology should be implemented.
Coaxial backbone cable may be implemented using a star or bus topology.
lnterbuilding Cabling Protection
When buildings are connected with interbuilding cabling, the applicable fusing
and voltage protection codes shall be followed. (see Entrance Protection Training
Module)
COMPONENT SPECIFICATIONS
Cable and associated components shall be suitable for use in the environment
to which they are exposed (e.g., ultra-violet (UV) resistant cable, listed
cable).
Unshielded Twisted-Pair (UTP) Cabling
UTP cable, equipment cords, patch cords and backbone cable shall meet all
specifications for the appropriate category within ANSI/TIA/EIA-568B.2.
Aerial Service Drop Wire
Aerial service drop wire is typically a small diameter, low pair-count cable
with limited unsupported span distances. It is used to feed a small number
of pairs from a higher pair-count cable into a single location. The maximum
span length shall not exceed 60 m (195 ft). Aerial service drop wire shall
meet the requirements of ANSI/ICEA 5-89-648.
UTP Connecting Hardware
All connecting hardware used with UTP cable shall meet the transmission and
reliability requirements of ANSI/TIA/EIA-568-B.2 At outlet locations, UTP
cable shall be terminated on an eight-position T568A telecommunications outlet
connector.
Eight-Position Telecommunications Outlet/Connector
The eight-position telecommunications outlet/connector shall:
comply with the modular interface requirements of IEC 60603-7
comply with T568A as specified in ANSI/TIA/EIA-568-B.2. (see Wiring Scheme
Training Module)
be able to withstand 200 insertions and meet the contact resistance requirements
of within ANSI/TIA/EIA-568-B when mated to an eight position plug
have the latching surface in the outlet connector be set back so that the
outlet/connector will not "capture" the plug clip.
Six-Position Telecommunications Connector (plug)
The tab width for a six-position plug shall be 6 mm (0.238 in) to 6.2 mm (0.243
in) in order to prevent damage to the 8 pin jack when inserting a 6 position
plug.
OPTICAL FIBER CABLES
Cable Transmission Performance
The interbuilding telecommunications cable shall comply with ANSI/ICEA S 87-640.
Outlet and intrabuilding optical fiber telecommunications cable shall comply
with ANSl/ICEA S-83-596. Each cabled fiber shall meet the graded performance
specifications of ANSI/TIA/EIA-568-B.3.
Physical Cable Specifications
The optical fiber cable construction shall consist of 50/125 µm, or
62.5/125 µm multimode optical fibers or singlemode optical fibers, or
a combination of these media. When fiber types are combineed within a cable
the cable shall be identifiable in accordance with ANSI/TIA/EIA-598-A. The
cable shall be listed and marked as required under the applicable electrical
code and local building code requirements.
Outlet and Intrabuilding Cable Specifications
See- Installation Requirements for Outlet and Intrabuilding Cable
Interbuilding Optical Fiber Cable Specifications
Interbuilding fiber optic cable shall:
meet with ANSI/ICEA S-87-640
have a water-block construction
have a minimum pull strength of 2670 N (600 lbft)
not exceed the bend radius recommendation provided by the cable manufacturer.
In the abscence of a recommendation from the manufacturer, then the cable
bend radius shall not exceed 20 times the cable's outside diameter when subjected
to tensile loading up to the cable's rated limit, or 10 times the cable's
outside diameter when not subjected to a tensile load.
Drop Cable
Drop cables are typically small diameter, low fiber count cables with limited
unsupported span distances. They are used to feed a small number of fibers
from a higher fiber count cable into a single location, Drop cable shall have
a minimum pull strength of 1335 N (300 lb/ft).
Equipment and Patch Cords
These cords are used to connect optical fiber links at cross-connects and
interconnects, and as equipment cords used to connect telecommunications equipment
to outlet or backbone cabling.
Patch Cord Cable
The optical fiber patch cord shall:
be a two-fiber cable, of the same fiber type as the optical fiber cabling
indoor construction
Patch Cord Connectors
The connector on an optical fiber patch cord allows for connection and reconnection,
and ensures that polarity is maintained. Patch cord connectors shall meet
the requirements of Annex A of the original standards documentation.
Termination Configuration
Proper polarity of optical patch cords shall be maintained by using a cross
over orientation, whether they are used for interconnection or cross connection.
In a cross over orientation of a two-fiber cable, each termination position
is labelled as Position A and Position B. When two cords are joined together
via an adapter, Position A on one cord is terminated with Position B on the
other cords. Each end of the fiber cord shall be identified with the position
designation. For simplex connectors, the connector that plugs into the receiver
shall be considered Position A, and the connector that plugs into the transmitter
shall be considered Position B.
CONNECTING HARDWARE
Duplex and multi-fiber connector designs may be used provided that the connector
design meets the performance requirements specified within Annex A of the
original specification documents, and ANSI/TIA/EIA-604 .
An adapter is the device used to join two like fiber optic connectors. The
most often used adapters are the SC and the ST. Hybrid adapters, although
not popular, are used to join two different fiber optic connectors.
Connector and Adapter
The connector and adapter shall:
be capable of simplex, or duplex, or multi-fiber optical fiber connection
shall meet the requirements specified in Annex A of the original standards
documentation labelled as positions "A" and "B" and labelled
either in the factory or field
Identification
The multimode strain relief boot, and multimode adapter shall be beigh in
color. The singlemode strain relief boot and singlemode adapter shall be blue
in color.
Telecommunications Outlet
The telecommunications outlet shall:
house two optical fibers and their connectors
have the ability to secure the optical fiber cable
provide for a bend radius of no less than 25 mm (1 in).
Optical fiber splice
Optical fiber splices, fusion or mechanical, shall not exceed a maximum optical
attenuation of 0.3 dB when measured in accordance with standard factory or
field testing methods.
75-0hm Coaxial Cabling
Many coaxial cables are prefixed with the letters "RG". These letters,
according to Newton's Telecom Dictionary stand for Radio Guide and was established
by the United States military. The "Series" designation is used
in this standard to ensure a consistent grade of performance. Cable performance
is much more important in today's applications than ever before. Applications
such as voice and data require proper shielding to prevent noise on the return
path. The SCTE speicifes a minimum shield construction consisting of a laminated
metal tape and a 60% coverage braid, i.e. a dual shield construction. Broadband
services extending up to 1 GHz, coaxial cables with tri-shield or quad shield
construction are recommended.
Coaxial cable, other than backbone:
shall be either Series 6 or Series 11 per the corresponding specifications
within SCTE IPS-SP-001.
Coaxial Equipment and Patch Cords Shall:
be assembled from Series 59 or Series 6 coaxial cable
be fitted with "F" male connectors
be one-hundred percent tested for electrical continuity
shall satisfy the Series 59 requirements of Bellcore, GR-1503-CORE and SCTE
IPS-SP-404
be installed according to SCTE IPS-SP-401.
Coaxial Backbone Cable
Coaxial backbone cable shall:
be either Series 6, Series 11, or Hard-line Trunk cable.
meet the corresponding specifications within SCTE IPS-SP-001 for Series 6
and Series 11 cable
meet the requirements of SCTE IPS-SP-100 for Hard Line Trunk cable.
COAXIAL CONNECTING HARDWARE
Coaxial Cable, Outlet and Distribution Device Connectors
Series 59, Series 6, and Series 11 cables shall be connectorized with an "F"
type connector compliant with SCTE IPS-SP-401.
Hard-line Trunk cables may be connected with an "N" type connector.
cable at the outlet and DD shall be fitted with a female "F" connector
compliant with SCTE IPS-SP-401.
Coaxial Outlet and Distribution Device Termination
An impedance matching 75-Ohm termination cap or device should be attached
to each:
unused coaxial outlet/connector
unused energized coaxial connector that is part of the connecting block, splitter,
amplifier, or similar electronic equipment.
INSTALLATION REQUIREMENTS
premises cabling shall be disconnected at the demarcation point or ADO during
any cabling operations
other electrical sources (e.g., a low voltage transformer) shall also be disconnected
testing premise cabling shall follow Annex B of the original standards documentation.
Cable Placement
Cable should be placed:
in a well ordered fashion to facilitate fault correction and moves, adds and
changes.
to eliminate cable stress such as that caused by tension in suspended cable
runs
avoiding tightly cinched bundled cables so as not to exceed the minimum bend
radius requirements of the cable so as not to deform the cable's outer jacket
All cabling shall comply with applicable codes and regulations.
Other Installation Requirements
pathways shall be firestopped as per applicable building codes.
secondary protectors shall be installed in series with the indoor telecommunications
cabling between the primary protector and the distribution device secondary
protectors shall be listed for the purpose and shall be compatible with the
primary protector.
Grounding and Bonding
Grounding and bonding systems are an integral part of the specific signal
or telecommunication cabling system that they protect. In addition to helping
protect personnel and equipment from hazardous voltages, a proper grounding
and bonding system may improve electromagnetic compatibility. Improper grounding
and bonding can produce induced voltages that can disrupt other telecommunications
circuits. Grounding and bonding shall meet the requirements and practices
of applicable authorities or codes.
Separation Distance from Electrical Power
Separation of telecommunications cable with respect to electrical power conductors
shall:
meet applicable electrical codes
have a minimum of 50mm (2 in) separation when cables with metallic components
are placed alongside unshielded electrical power conductors inside wall space
or ceiling space.
Reducing Noise Coupling
Interference from electrical power wiring and motors or transformers may be
reduced by:
keeping branch circuit conductors taped, sheathed, bundled, taped or twisted
together using surge protectors
using enclosed, grounded metallic raceway or conduit
crossing communications cable and electrical cable at 90 degrees.
Administration
Cabling systems shall be installed in accordance with color-coding,
labeling, and documentation specified in ANSI/TIA/EIA-606.
100-0hm UTP Cabling Shall:
have a minimum bend radius of 4 times the OD of the cable
use a maximum pulling tension of 110N (25 lbf)
Connecting hardware termination
Connecting hardware should:
be terminated with connecting hardware of the same category or higher.
meet the minimum performance of components and cables of the system. A Category
3 component on a Category 5e system renders the system to Category 3 levels.
have the performance category marked on the connecting hardware or noted in
the telecommunications records.
only have as much cable jacket stripped back as required to terminate connecting
hardware.
Connecting hardware termination shall:
have a minimum of 200 mm (8 in) of excess cable shall be stored at each outlet.
have a maximum untwisting of the pairs for Category 5 and 5e cables no greater
than .5" and no greater than 75mm (3 in) for Category 3 cables.
Cross-Connect Jumpers and Patch Cords
Should be:
the same category or higher as the outlet cables to which they connect.
factory terminated.
OPTICAL FIBER
Outlet and Intrabuilding Cable
Shall:
not have a bend radius smaller than the manufacturer's recommended minimum
bend radius for the cable.
not have 2- and 4-fiber cables installed with a bend radius less than 25mm
(1 in) under no-load conditions.
not have 2- and 4-fiber cables intended to be pulled through pathways during
installation installed with a bend radius less than 50 mm (2 in) under a minimum
pull load of 222 N (50 ft/lb).
not exceed the manufacturer's bend radius recommendation for intrabuilding
cables.
If a recommendation is not provided or known, then the cable bend radius shall
not exceed 15 times the cable's outside diameter when subjected to tensile
loading up to the cable's rated limit, or 20 times the cable's outside diameter
when not subjected to a tensile load.
Interbuilding Cable
Interbuilding backbone optical fiber cables shall:
not exceed the bend radius recommendation provided by the cable manufacturer.
have a bend radius of 20 times the OD of the cable under the rated tensile
load, and 10 times the OD under no load conditions where the bend radius parameters
are unknown.
Connecting Hardware Termination
Fiber optic cable terminations shall:
be contained in a telecommunications outlet box or mounting bracket.
have a minimum of 1 m (3.3 ft) of two-strand optical fiber cable, or two buffered
optical fibers accessible for termination purposes.
have the correct adapter orientation and optical fiber cabling in order to
maintain the overall polarity of the sysem.
be installed so as to pair an odd numbered fiber with the next consecutive
even numbered fiber (i.e., fiber I with 2, 3 with 4, and so forth) to form
two fiber transmission paths. The odd numbered fibers will be deemed to be
Position A at one end and Position B at the other end, and the even numbered
fibers will be Position B at one end and Position A at the other end.
Patch Cords
Patch cords will designated with a Postion A and a Position B to maintain
overall system polarity. When patch cords are two simplex connectors, one
connector shall be labeled A and the other B. When the electronics interface
is a duplex connector, the connector that plugs into the receiver shall be
considered Position A, and the connector that plugs into the transmitter shall
be considered Position B.
75 OHM COAXIAL CABLE
Minimum Bend Radius
The minimum bend radius shall:
not be less than 20 times the OD of the cable when being pulled.
not be less than 10 times the OD of the cable when placing or dressing the
cablel
be reduced if recommended by the manufacturer.
Table 4: Maximum Pulling Tension for Coaxial Cable
Cable Type Maximum Pulling Tension
Series 6 150 N (35 Ibf)
Series 11 400 N (90 Ibf)
Hard Line See Manufacturer Recommendations
Connecting Hardware Termination
A minimum of 200 mm (8 in) of excess cable slack should be provided at each
outlet.
Patch cords
Series 59 and Series 6 cable shall be used for patch cords and cross-connect
jumpers. Factory terminated patch cords and jumpers are recommended, If assembled
by the installer, care must be taken that the proper size 'F type connector
is used.