Splicing

Overview

Splicing can be defined as the joining of two conductors or fibers together to restore the conductor continuity between two points. Since most cables are constructed of more than one or two conductors or fibers, splicing generally involves more than one or two pairs, and generally involves restoring the integrity of the cable sheath, armour and shield.

Splicing begins with the joining of the conductors with a single splice. In copper splicing one of the types of splices used is the 3M Scotchlok. Once all of the conductors have been spliced they will be inserted into the splice enclosure which is selected by the location of the splice enclosure. In a fiber optic splice, the fibers are joined by a mechanical or fusion splice and then inserted into a splice tray.

For the purpose of this Standard, the term splice closure shall include bonding hardware, sealing materials and the closure housing.

COPPER SPLICING

General

Copper splice connectors:

Splicing connectors for OSP:

Due to the variety of connectors, manufacturers shall provide all of the necessary tooling required to terminate their connectors.

Materials

Metal components shall:

Insulating materials:


Plastic materials shall:

Connector filling compounds shall:

Transmission Performance Markings

If the manufacturer so desires it may mark its splicing hardware with its level of transmission performance and these markings shall be visible during installation. It is suggested that the markings consist of:

"Cat 3" for category 3 components
"Cat 4" for category 4 components
"Cat 5" for category 5 components

Tensile Strength

The tensile strenght of a splice is the force required to pull the wire in the opposite direction of entry to the splice. The pull out strength is expressed as a percentage of the strength required to break an unspliced wire. The minimum breaking strength for a 19 AWG wire is 60% of 19 AWG wire breaking strength. The breaking strength for smaller gauge splices is 75% of the wire breaking strength.

Insulation Resistance

Splicing connectors that are to be used in severe service conditons shall be tested for moisture resistance. This test involves immersing the moisture filled or resistant connector tap water for a period of one week. The insulation resistance shall then be measured between each conductor and the water bath with 250 Vdc applied. No more than 10 percent of the conductors shall be less than 10 6 ohms, not more than 25 percent shall be less than 10 8 ohms, and the remainder shall be greater than 10 9 ohms. After drying, the test units shall be restored to greater than 10 9 ohms. Those that fall below 10 8 ohms shall be inspected for corrosion. If there is evidence of corroision, the unit shall be deemed to have failed the test. It should be noted that this is a criteria for the manufacturer to follow and not the installation contractor.

Salt Fog Exposure

Terminated (or spliced) filled samples shall be exposed to salt fog per ASTM B 117 for a period of 48 hours. The resistance though each splice shall not increase by more than 2 milli-ohms as a result of this exposure.

OSP Twisted-Pair Cross-Connect Jumpers

Cross-connect jumper wire shall be wire of the same or higher transmission category as the cross-connect block so as to maintain the overall performance of the system. The twist shall be maintained to within 13 mm (0.5 in) of the entry into the cross-connect block.

INSTALLATION REQUIREMENTS

Cable Splices for BBOSP

There are two type of splices, the butt splice (preferred) and the inline splice. An in-line splice method can also be used if the conductors are spaced close together, i.e., no open loops. The amount of untwisting of the conductor pairs shall be kept at 13 mm (0.5 in) maximum. Pair splices should be staggered within the splice closure to help maximize performance.

Bridge-Taps

Bridge taps may be used for low-frequency analog circuits, but are not recommended for OSP circuits or high frequency digital circuits.

Binder group integrity

25-pair binder groups should not be split between termination points.

OSP Twisted-Pair Testing

OSP twisted pair cables are not subject to the same tests as horizontal UTP cables are. The primary field test parameters for OSP twisted-pair cabling are:

S PLICE ENCLOSURES

General

Splice cases, splice closures or splice enclosures are the more common names used to describe the devices used to house splices. These names may refer to devices for both copper and fiber.

Materials

In copper and fiber optic splice enclosures the materials used in shall exhibit the following properties:

Metal components shall:

Non-metallic components shall:

COPPER TWISTED-PAIR COPPER ENCLOSURES

General

Outdoor closures may be installed:

The splice enclosures are should be expected to operate at temperatures between -40ºC and 65ºC (-40ºF and 150ºF) without degradation in performance. The enclosure is also expected to function normally if subjected to other forms of environmental factors such as ice, submersion in water and heat sources.

A splice closure is used restore integrity of the cable sheath's electrical and mechanincal properties following a sheath opening to:

Aerial Copper Closures/Terminals

Strand Mount

There are a variety of design configurations available for strand mounted enclosures, depending on the application. Regardless of the overall design, strand mount devices:

Some terminals designed for strand mounting may also be pole mounted, eg: at a dead end, or where a transition from aerial to buried cable is required.

Special Testing

Special tests for aerial copper closures/terminals can be found in Bellcore document TR-NWT-00014

Buried Service Wire Closures

Application

Buried service wire closures:

Special Tests

Special tests for buried service wire copper closures are found in Bellcore document TR-NWT-000251.

BURIED/UNDERGROUND/VAULT SPLICE CLOSURES

Closure Housing

The closure housing shall be compatible with all materials used in the construction of cable, filling compounds, bonding and grounding devices, chemicals, and sealants which the closure would contact under normal use. Secondary corrosion protection should not be required.

Installation Requirements

The closure:

Special Tests

Special tests for buried/underground/vault copper splice closures can be found in Bellcore documents TR-NWT-000014, TR-NWT-000251 and PUB 55004